• KYN28-12(GZS1) Armored Withdrawable AC Metal-Enclosed Switchgear
KYN28-12(GZS1) Armored Withdrawable AC Metal-Enclosed Switchgear
+

KYN28-12(GZS1) Armored Withdrawable AC Metal-Enclosed Switchgear

This product meets the requirements of standards such as IEC 298 and GB 3906, featuring interlocking functions that prevent the load-carrying operation of circuit breaker trolleys, avoid unintended tripping or closing of circuit breakers, block the closing of circuit breakers when the grounding switch is in the closed position, prevent accidental entry into live compartments, and ensure the grounding switch remains open under energized conditions. It is compatible with ABB’s VD4 vacuum circuit breakers, Xiamen Huadian VEP, Siemens 3AH, Schneider EV-12, and GE VB2 circuit breakers, as well as domestically produced VS1 vacuum circuit breakers—making it a truly high-performance distribution device.

Still deciding? Get a sample first—contact us!

Keywords:

High-Voltage Switchgear

Box-type substation

  • Product Description
  • Product Overview

    This product meets the requirements of standards such as IEC 298 and GB 3906, featuring interlocking functions that prevent the operation of circuit breaker trolleys under load, avoid unintended tripping or closing of circuit breakers, block the closing of circuit breakers when the grounding switch is in the closed position, prevent accidental entry into live compartments, and ensure the grounding switch cannot be closed while energized. It is compatible with ABB’s VD4 vacuum circuit breakers, Xiamen Huadian VEP, Siemens 3AH, Schneider EV-12, and GE VB2 circuit breakers, as well as domestically produced VS1 vacuum circuit breakers—making it a highly reliable and superior-performing distribution device.

    Meaning of the Model

    Technical specifications

    Project Unit Data
    Rated Voltage kV 3.6, 7.2, 12
    Rated Insulation Level 1-minute power frequency withstand voltage kV 24, 32, 42
    Lightning Impulse Withstand Voltage kV 40, 60, 75
    Rated frequency Hz 50
    Rated current A 630, 1250, 1600, 2000, 2500, 3150
    Rated Thermal Current (RMS/s) kA 25/4, 31.5/4, 40/3
    Rated Dynamic Stability Current (Peak) kA 63, 80, 100
    Protection Level   The enclosure is rated IP4X; the circuit breaker door, when open, provides an IP2X rating.

    External Dimensions and Mounting Size

    Project Dimensions/Weight
    Height (mm) The branch busbar's rated current reaches 1250 A. 2300 (2200)
    Width (mm) Thermal stable current: 31.5 kA 800 (650)
    Busbar rated current exceeding 1600A 1000
    Depth (mm) Cable entry and exit 1300, 1500
    Overhead incoming and outgoing lines 1660
    Weight (kg)   800–1200

Recommended Products